Russell Hernandez Mar 1, 2018 6:46 PM
To
jeffrey E.
B
Bill Hague Mar 1, 2018 7:11 PM
Well.
No surprises here.
The outstanding issue I see here has to do the Megger test (insulation test). It should be tested BEFORE, any work is done to the generator end windings.
A subsequent test, after the work is done, will then let us know if this cleaning did any HARM to the operational function of the units during the cleaning, in a before and after factual test. It will eliminate any he said he said and finger pointing.
Thats my opinion of the report.
I look forward to your insights.
R